How to compare a lighting substitute against the basis of design
About the example. Both products in this guide are fictional: Example Lighting LIN.UP and Sample Lighting Co. LN-2. The numbers illustrate the method. They are not test results, and neither company is a chatLED customer.
What you are deciding
A substitution request asks you to accept a different luminaire from the one you specified. The basis of design is the product your drawings, calculations and details were built around. The substitute is the product someone proposes in its place, usually on a submittal.
The question is narrower than "is this a good product". It is whether the substitute does what the basis of design does, in this project, in every respect the design depends on. Jean Sundin, writing in Architect magazine, put it this way: "no two products are truly 'equal'". Her advice was to ask for an equivalent and to evaluate the photometric properties against the performance criteria.
Use three results, not two
Most comparison tables mark each line as a match or a difference. That hides the most common problem, which is a value the substitute's sheet does not publish. Use three results.
- Match. Both sheets publish the value and the values agree, within a tolerance you set before you start.
- Differs. Both sheets publish the value and the values disagree. This is a verified mismatch.
- Not published. One sheet has no value. This is missing data. It is a question for the manufacturer, not a pass and not a fail.
A blank treated as a match approves a product on no evidence. A blank treated as a difference rejects one for a gap in its paperwork. Keep the third result separate until someone answers it in writing.
A worked comparison
The basis of design is a 4 ft LIN.UP pendant at 3500K, medium output. The proposed substitute is a 4 ft LN-2. The tolerance set in advance is 5% on delivered lumens and an exact match on everything else.
| Spec | Basis of design: LIN.UP | Substitute: LN-2 | Result |
|---|---|---|---|
| Distribution | Indirect | Indirect | Match |
| Nominal length | 4 ft | 4 ft | Match |
| Delivered lumens | 2,400 lm | 2,250 lm | Differs: 6.25% lower |
| Input power | 22 W | 24 W | Differs: 2 W higher |
| Efficacy | 109.1 lm/W | 93.8 lm/W | Differs |
| CCT | 3500K | 3500K | Match |
| CRI | 90 | 90 | Match |
| R9 | 50 or higher | Not on the sheet | Not published |
| Voltage | 120/277V | 120/277V | Match |
| Dimming | 0-10V to 1% | 0-10V to 10% | Differs |
| Finish | White | White | Match |
| Warranty | 5 years | 5 years | Match |
Seven lines match, four differ and one is not published. Efficacy is delivered lumens divided by input power: 2,400 ÷ 22 = 109.1 and 2,250 ÷ 24 = 93.8.
The count does not make the decision. Read the four differences against the design.
- Delivered lumens. The substitute is 6.25% lower, outside the 5% tolerance. Re-run the calculation for the rooms that were close to their target. If they still pass, record that. If not, ask whether a higher output option exists.
- Input power. Two more watts per fixture changes the lighting power density. Multiply by the quantity and check the energy code margin.
- Dimming. A 10% minimum is visible in a conference room and may not matter in a corridor. Check which spaces carry this type.
- Efficacy. 93.8 lm/W against 109.1 follows from the two lines above. Check it against any minimum efficacy the specification sets.
The R9 line is not a difference yet. Send one question: what is the R9 value for this configuration, and where is it published? Until the answer arrives, the line stays open.
The comparison table is available to download as a spreadsheet file: substitution-comparison-example.csv.
A review checklist
Use the same list for every substitution on a project, so that two reviewers reach the same answer.
- Compare exact configurations. Use the full part number on each side, not the product family. Output, CCT and driver all change the published values.
- Confirm both sheets are current. Note the revision date of each. A superseded sheet is a common source of false differences.
- Photometry. Compare delivered lumens, distribution and, where glare matters, UGR or shielding angle. Request the IES file and re-run calculations for critical spaces.
- Color. CCT, CRI, R9 and color consistency (SDCM or MacAdam steps), each for the configuration proposed.
- Electrical and controls. Voltage, input power, dimming protocol, dimming range and driver location. Confirm the driver works with the specified control system.
- Physical fit. Dimensions, weight, mounting method, recess depth, and the ceiling or wall details already drawn.
- Ratings and listings. Location rating, IP and IK where required, and the listings the project specification names. Check these on the sheet itself.
- Options and accessories. Emergency, sensors, finishes and lengths the project uses. A product family can match while the needed option does not exist.
- Lead time and warranty. Ask for both in writing for the configuration and quantity on the schedule.
- Record the result per line. Match, differs or not published, with the page of each sheet the value came from.
Who decides
A table shows what changed. It does not approve anything. The lighting designer or specifier of record decides whether each difference is acceptable for the design, and the manufacturer confirms any value that is not on its published sheet. Keep the table, the open questions and the answers with the project record, so that the reason for an approval or a rejection can be found later.
chatLED's Substitution Analysis service lays out a basis of design and a substitute side by side from each manufacturer's published data, with the source shown for each value.
Next step
Ask the chatLED Agent about a product you are reviewing. Answers cite the manufacturer's spec sheet.